MA
Maria Alvarez
Class A Operator
Field Records

Inspection Log

  1. Monthly Walk-Through
    Austin Central Distribution Terminal · Austin, TX · Inspector: M. Alvarez
    9/9/2026
    Pass with Notes

    Minor staining under T-102 dispenser sump — cleaned and documented.

  2. Annual Operability
    Round Rock Fleet Depot · Round Rock, TX · Inspector: R. Kimura
    9/3/2026
    Pass

    All overfill alarms tested. Release detection system reset performed.

  3. Cathodic Protection
    Austin Executive Airfield Fueling · Austin, TX · Inspector: T. Odum
    8/26/2026
    Pass

    Reference cell -0.92V. Within spec.

  4. 3-Year Line Test
    Manor Rail Yard · Manor, TX · Inspector: D. Whitfield
    8/13/2026
    Fail

    Line 2 failed 0.1 gph test. Line locked out; retest scheduled.

  5. Spill Bucket
    Cedar Park Marine & Fleet Fuel · Cedar Park, TX · Inspector: M. Alvarez
    8/6/2026
    Pass with Notes

    Water accumulation in M-1 bucket. Evacuated and inspected liner.

  6. Overfill
    Georgetown Cardlock · Georgetown, TX · Inspector: J. Prieto
    7/25/2026
    Pass

    Automatic shutoff device functioning at 95%.