Field Records
Inspection Log
- Monthly Walk-ThroughAustin Central Distribution Terminal · Austin, TX · Inspector: M. Alvarez9/9/2026Pass with Notes
Minor staining under T-102 dispenser sump — cleaned and documented.
- Annual OperabilityRound Rock Fleet Depot · Round Rock, TX · Inspector: R. Kimura9/3/2026Pass
All overfill alarms tested. Release detection system reset performed.
- Cathodic ProtectionAustin Executive Airfield Fueling · Austin, TX · Inspector: T. Odum8/26/2026Pass
Reference cell -0.92V. Within spec.
- 3-Year Line TestManor Rail Yard · Manor, TX · Inspector: D. Whitfield8/13/2026Fail
Line 2 failed 0.1 gph test. Line locked out; retest scheduled.
- Spill BucketCedar Park Marine & Fleet Fuel · Cedar Park, TX · Inspector: M. Alvarez8/6/2026Pass with Notes
Water accumulation in M-1 bucket. Evacuated and inspected liner.
- OverfillGeorgetown Cardlock · Georgetown, TX · Inspector: J. Prieto7/25/2026Pass
Automatic shutoff device functioning at 95%.